博狗直营

耐用稳定,有效提高您的生产效率 Ignition, fire detection equipment, combustion control system production service manufacturers are durable and stable, effectively improving your production efficiency
13720404230 National Service Hotline: 029-68822180 13720404230
燃信热能火焰检测器

support hotline

029-68822180
  • RXBQ-102S熄火保护报警控制箱
  • RXBQ-102S熄火保护报警控制箱
RXBQ-102S flameout protection alarm control box
RXBQ-102S flameout alarm control box is a flame monitoring and alarm system specially designed and developed according to the needs of petrochemical, metallurgy, coal chemical, ceramics and other industries. The product is equipped with a flame monitor, which is simple, reliable, and easy to use and maintain. It is suitable for the flame monitoring and flameout alarm of various gas, oil burners and roasters.
National Hotline

029-68822180

Functional Overview

紫外线火焰监测器、断路器、中间继电器、时间继电器、按钮、指示灯等控制元件。 The control box is equipped with RXBQ-102S ultraviolet flame monitor, circuit breaker, intermediate relay, time relay, button, indicator and other control elements. 紫外线火焰监测器采用我公司高性能产品,电器元件均采用国内知名品牌,以确保设备运行可靠。 The RXBQ-102S ultraviolet flame monitor in the box uses our high-performance products, and the electrical components are all well-known domestic brands to ensure reliable operation of the equipment. The system has flameout interlock protection. When an accidental flameout occurs during system operation, the gas solenoid valve can be closed in time to ensure the safety of the system, and the fire and flameout signals can be uploaded to the upper computer in the form of switching values, which is convenient for operators to monitor. The control system is simple, safe and reliable.

RXBQ-102S熄火保护报警控制箱

The main technical parameters

Working power: 220VAC / 50Hz

Power consumption: 100W

Flame response time: see fire response ≤1s

Flameout response 1 ~ 3s

Display: The power indicator (red) is on when the control cabinet is powered on

Turn on the operation knob (the white indicator is on)

The fire indicator (green) is on when the fire responds

The fire indicator (green) goes out when the flameout response occurs, and the sound and light alarm alarms

Output:

1.Fuel solenoid valve power supply AC220V

2. A group of fuel valve interlocking signals (passive normally open contact of relay, capacity 220VAC · 5A)

3. Real-time flame signal relay normally closed, normally open passive contact, each group has a capacity of 220VAC · 5A

Normally closed contact is closed and normally open contact is opened during flameout response

Normally closed contact opens when the fire responds, normally open contact closes

Working environment temperature: monitor and UV probe: -20 ℃ ~ 80 ℃

Dimensions: 400 × 300 × 200 (mm)

Mounting hole size: Probe mounting thread M20 * 1.5

Monitor Model: UV Probe

Installation and wiring

Detection probe installation (special prompt)

BWZJ-13 UV flame monitor is a non-contact flame monitor. When installing, please point the probe at the flame. The maximum temperature used by the probe is 80 ° C. When the user uses it on a burner or other high-temperature equipment, the detection channel in front of the probe must be ventilated and cooled. The diameter of the detection channel is not less than Φ18, and the mounting thread of the probe is M20 × 1.5.

Installation of the control box

The structure of the control box is wall-mounted. Use four M8 bolts to install the device at a suitable location on the site. The installation position must be protected from high temperature, strong vibration or impact.

For wiring, refer to the wiring diagram in the control box.

Power 220VAC / 50Hz 6A If the AC power used by the user is an ungrounded power supply, such as an isolation transformer, please ground one line of the power supply.

Note that the flame signal line and the high-current power line cannot be routed in a pipe, but should be routed separately. After installing and confirming that the wiring is correct, you can run with power.

Box face

箱面部置

Operating procedures

1. Close the power circuit breaker of the control box, and the power indicator light is on.

2. Turn the operation switch to the on state, the operation indicator light is on, and the fuel valve is opened at the same time. (Reserve the ignition time for 10 seconds, keep the fuel valve open until the ignition time ends in 10 seconds. After the ignition time is over, the fuel valve is The flame signal is used to open or close the fuel valve. For example, the fire remains open and closes without fire.) The flame monitoring system starts to run. If a fire is detected, the fire indicator lights up. Conversely, if no fire is detected or the flame is extinguished, the fuel solenoid valve is automatically closed and the audible and visual alarm lights are sounded to remind the operator that the flame is extinguished. After the operator is in place, he can turn the operation switch to the off position, the alarm beep will stop, and the operation indicator will go out. After the operator removes the fault, the system operation can be restarted.

debugging

To improve monitoring sensitivity, the sensor cable should not be mixed with other power or signal lines.

RXBQ-102S flameout protection alarm control box has been debugged at the factory. Generally, it can be used after installation. If the probe is too far away from the monitor and the distributed capacitance caused by the wiring is too large, a fire is displayed without a flame. Please open the module and slowly adjust the matching potentiometer in the middle of the module counterclockwise until the red indicator light is off and the relay is released. So far, the module is debugged, and the module cover is closed. Please pay attention not to overshoot when debugging, overshoot affects the monitoring sensitivity.

After the installation is completed and the wiring is correct, you can run it with power and the power indicator is on. On the panel of the control box, there is a running switch. Turn the switch to the working state. The running indicator is on. When there is a flame signal, the fire indicator is on. When there is no flame signal, the fire indicator is off and the audible and visual alarm sounds.

Troubleshooting

The burner has no fire, but the monitor shows fire. This is the interference caused by the gradually increasing distributed capacitance of the monitoring line after it is wet. Please turn on the module and slowly adjust the potentiometer counterclockwise until the red indicator light is off and the relay is released.

The burner has fire, but the monitor shows no fire. There may be two reasons. One is that the probe lens is covered by dust. Please clean the quartz lens of the probe. The other is the impedance matching potentiometer overshoot. Please open the module and adjust the potential slowly clockwise. Until the red indicator light is on and the relay is closed.

If the lens of the probe is accidentally broken during installation or use, do not replace it with ordinary glass sheets, because ordinary glass sheets cannot transmit ultraviolet rays generated by flames.

Note: In any case, it is not recommended that the customer open the monitor module to adjust the sensitivity of the product. If adjustment is required, please contact our technicians for guidance.

10 years of intensive farming, a trusted manufacturer

执着品质

10年经验技术团队,产品更放心 Dedicated to a 10-year experience technical team, products are more assured

Ignition equipment: up to 100% ignition success rate , can withstand high temperature of 1300 ℃, more stable performance

Fire detection equipment: research and development process to improve the reliability of equipment operation and the accuracy of detection to ensure the safety of operations

Combustion control system: more energy efficient than traditional design, for the purpose of optimizing the combustion efficiency of the boiler , environmental protection and emission reduction

厂家直供

成本更低,满足急单、大订单需求 Manufacturers' direct supply costs are lower, which meets the needs of urgent orders and large orders

Plant of 1200 square meters, 100+ production staff, to meet customer demand for urgent orders

With an annual output of 5,000 units, the production capacity is higher than peers, and it can meet the needs of large orders at any time.

Complete equipment, the introduction of domestic and foreign equipment production lines, fully automated production

客户为本

提供上门指导安装,服务更贴心 Customers provide on-site guidance for installation and service is more intimate

Free customized solutions , more suitable product recommendations

According to the actual situation of customers, provide on- site guidance and installation services to make the product operate normally

24-hour online customer service, timely collect and feedback customer questions , answer questions

Contact Ranxin Thermal

Xi'an Ranxin Thermal Energy Engineering Technology Co., Ltd.

  • Sales Center: 029-68822180
  • Sales one: 137-2040-4230
  • Sales Department 2: 186-2937-4231
  • Technical consultation: 136-7926-6047
  • Email: 1440407780@qq.com
Purchase: RXBQ-102S Flameout Alarm Control Box
    • *

    • *

    • *

Hot product
RXFY-12防爆遥控高能点火器

RXFY-12 explosion-proof remote control high-energy igniter

RXFY-12 explosion-proof remote control high-energy igniter is equipped with high-energy igniter, remote-control transmitter, time relay, button, indicator and other control elements. It can realize local ignition, remote ignition and system running status display, and the operation is simple, safe and reliable. It is mainly used for the auto-ignition of gas, fuel oil industrial burners, flaring torches and fire drills. It has the advantages of reliable ignition and long life. Metallurgy, ceramics, environmental protection and energy industries.
RXFND-20便携式防爆高能点火器

RXFND-20 portable explosion-proof high-energy igniter

RXFND-20 portable explosion-proof high-energy igniter is designed and manufactured by our company's high-energy igniter and imported military PWF power chip synthesis technology. Its performance is superior to ordinary PWM inverter technology, and has the characteristics of high output ignition energy and fast ignition frequency. The panel displays the real-time ignition signal. Portable explosion-proof high-energy igniter is a portable rechargeable ignition device that does not need to increase the power supply. One charge is based on working conditions for at least one month, and it is small in size, large in ignition energy, long in service life, and easy to carry. It has been widely used. Used in petroleum, chemical, metallurgy, glass, ceramics and other industries
RXFND-12防爆便携式高能点火器

RXFND-12 portable explosion-proof high-energy igniter

RXFND-12 portable explosion-proof high-energy igniter is designed and manufactured by our company's high-energy igniter and imported military industrial PWF power chip synthesis technology. Its performance is superior to ordinary PWM inverter technology. It has the characteristics of high output ignition energy and fast ignition frequency. The panel displays the real-time ignition signal. Portable explosion-proof high-energy igniter is a portable rechargeable ignition device that does not need to increase the power supply. One charge is based on working conditions for at least one month, and it is small in size, large in ignition energy, long in service life, and easy to carry. It has been widely used. Used in petroleum, chemical, metallurgy, glass, ceramics and other industries
RXGD-20高能点火器

RXGD-20 high energy igniter

RXGD-20 high-energy igniter is mainly used for automatic ignition of large light oil, low heating value gas, heavy oil industrial burners in power plant boilers, petrochemicals and other industries. It has the advantages of reliable ignition and long life, high temperature resistance at the ignition end, coking resistance, and self-cleaning. ability.

Xi'an Ranxin Thermal Energy Engineering Technology Co., Ltd., located in Xi'an, is a high-tech company engaged in the design, development, production, sales, installation and commissioning of electronic ignition equipment, flame detection equipment, and automatic control systems for ignition and combustion processes .