燃信热能火焰检测器

National Service Hotline

029-68822180

UV flame monitor

Ultraviolet flame detector: It consists of an ultraviolet flame detector controller, a UV probe, and a detection cable.

It is used for the flame monitoring of the burners of gas and oil industry boilers. The monitor is only sensitive to the ultraviolet rays generated, has no response to the high temperature radiation of the lights and the furnace, and has strong anti-interference.

Function: Control the igniter to automatically ignite, and automatically open the fuel valve during ignition. If the ignition is not ignited within the set time, the controller automatically closes the fuel valve and alarms. If the ignition is successful, the normal fuel supply is maintained. ).

installation:

1. Ultraviolet flame detector is a non-contact flame detector. Please point the probe at the flame when installing.

2. The maximum temperature used by the probe is 100 ° C. When the user uses it on a burner or other high-temperature equipment, the detection channel in front of the probe must be ventilated to prevent the sensor from being damaged by high-temperature conducted radiation in the furnace. The cooling air must be dry and clean.

3. The diameter of the detection channel is not less than Φ18, and the installation thread of the probe is M20 × 1.5.

model

RXZJ-102

RXZJ-102D

RXZJ-102A

RXZJ-102B

RXFZJ-102

RXFZJ-102D

RXFZJ-102A

RXFZJ-102B

RXZJ-102T

Operating Voltage

220V / AC ± 10%

24V / DC

24V / DC

220V / AC ± 10%

220V / AC ± 10%

24V / DC

24V / DC

220V / AC ± 10%

220V / AC ± 10%

output signal

Switch

Switch

4-20mA / switching value

4-20mA / switching value

Switch

Switch

4-20mA / switching value

4-20mA / switching value

Switch

Module volume

155 * 90 * 55

198 * 90 * 60

198 * 90 * 45

198 * 90 * 45

300 * 200 * 150

300 * 200 * 150

300 * 200 * 150

300 * 200 * 150

Detection probe

Probe mounting thread M20 * 1.5 Detection distance ≤11 meters

Types of

Split type

Split type Exd IIBT4 or Exd IICT4 (can be customized)

Integration


RXZJ-102紫外线火焰监测器

RXZJ-102 UV flame monitor

RXZJ-102 UV flame monitor for gas and oil industry burners ... [Details]
RXZJ-102A紫外线火焰检测器

RXZJ-102A UV flame detector

RXZJ-102A UV flame detector (4-20mA flame detector) ... [Details]

Xi'an Ranxin Thermal Energy Engineering Technology Co., Ltd., located in Xi'an, is a high-tech company engaged in the design, development, production, sales, installation and commissioning of electronic ignition equipment, flame detection equipment, and automatic control systems for ignition and combustion processes .